MODEL | DRX 300 H OPTI | DRX 400 H OPTI | DRX 500 H OPTI | |
---|---|---|---|---|
Air flow (100 Pa) | [m3/h] | 350 | 450 | 550 |
Performance range | [m3/h] | |||
Type of heat recovery system
|
[Pa] | 200 | 200 | 200 |
Heat recovery efficiency* | – |
diaphragmatic
|
diaphragmatic
|
diaphragmatic
|
Heat recovery efficiency*
|
[%] | 93,1 | 88,5 | 86,2 |
Energy consumption | [W] | 16-230 | 18-338 | 18-338 |
Power of the pre-heater
|
[W] | 500 | 500 | 500 |
Fan power consumption
|
[W] | 166 | 338 | 338 |
Sound power level
|
[dB(A)] | 60 | 60 | 60 |
Connection diameter
|
mm | 200 | 200 | 200 |
Connection system
|
– |
horizontal
|
horizontal
|
horizontal
|
Libra | kg | 60 | 60 | 60 |
|
WTA 5X20 250V F-6,3A | WTA 5X20 250V F-6,3A | WTA 5X20 250V F-6,3A | |
Rated supply voltage and frequency
|
V/Hz | 230/50 | 230/50 | 230/50 |
Type of exchanger
|
||||
Filter class
|
– | M-5/ePM10 | M-5/ePM10 | M-5/ePM10 |
Declared type | – | bi-directional | bi-directional | bi-directional |
Type of drive installed
|
– | stepless regulation of fan speed | stepless regulation of fan speed | stepless regulation of fan speed |
Declared maximum internal coefficients. and external air leaks |
[%] |
internal 1,35,
external 1,63
|
internal 1,00,
external 1,23
|
internal 0,78,
external 0,98
|
JZE class**
|
– | A | A | A |
* Test conditions according to PN-EN 13141-7 |
– | |||
** according to Regulation (EU) No. 1254/2014 | – |
Controller: